Study with the several resources on Docsity
Earn points by helping other students or get them with a premium plan
Prepare for your exams
Study with the several resources on Docsity
Earn points to download
Earn points by helping other students or get them with a premium plan
Community
Ask the community for help and clear up your study doubts
Discover the best universities in your country according to Docsity users
Free resources
Download our free guides on studying techniques, anxiety management strategies, and thesis advice from Docsity tutors
A comprehensive set of questions and answers related to the fire alarm tfm 12 exam, covering various aspects of fire alarm systems, including detectors, wiring, and regulations. It is a valuable resource for students preparing for the exam, offering insights into key concepts and practical applications.
Typology: Exams
1 / 14
This page cannot be seen from the preview
Don't miss anything!
25.What type shall plenum cable be? What substitutions are allowed? - Correct Answer-Power Limited Fire Alarm Plenum (FPLP) CMP can be substituted. 26.What type shall riser wire be? What substitutions are permitted? - Correct Answer-Power Limited Fire Alarm Riser (FPLR) CMP,FPLP,CMR can be substituted. 27.What type shall general purpose wire be? What substitutions are permitted? - Correct Answer-Power Limited Fire Alarm (FPL) CMP,FPLP,CMR,FPLR,CMG, and CM can be substituted. (All types) 28.What is the maximum voltage permitted through multi-conductor NPLFA cables? - Correct Answer-150 volts 29.What is the voltage rating of PLFA cables? - Correct Answer-Not less than 300 volts 30.Shall the voltage be marked on PLFA cables? - Correct Answer-No, because they may be misinterpreted and used for electrical applications. 31.What is a Spot Type Detector? - Correct Answer-A device in which the detecting element is concentrated at particular location. 32.What is a Digital Alarm Communicator Receiver? (DACR) - Correct Answer-a system component that accepts and displays signals sent over the public phone network from a DACT. (Le. ADT Monitoring center) 33.What is a Digital Alarm Transmitter? (DACT) - Correct Answer-A system component at the protected premises is connected to the detection devices. It has line seizure and can connect to a DACR. (le. DSC Impassa)
34.What is an Alarm Signal? - Correct Answer-A signal indicating an emergency that requires immediate action. 35.What is a supervisory signal? - Correct Answer-A signal that indicates the need for action in connection with the SUPERVISION of the fire equipment. 36.What is a trouble signal? - Correct Answer-A signal that indicates a FAULT with the fire equipment. It must have an audible signal, distinctive form alarm signals. 37.Does an exterior horn for a sprinkler system need to be supervised? - Correct Answer-Yes 38.Does a fire hood sprinkler system in a kitchen need to be monitored by the fire alarm system? - Correct Answer-Yes 39.What is a cloud chamber smoke detection? - Correct Answer-A detector that draws an air sample into high-humidity, low pressure chamber. The condition in the chamber cause the moisture in the air to condense on the smoke particles, forming a cloud. The density of this cloud is measured by a photoelectric principle, if it meets a certain criteria, an alarm is generated. 40.What is a ionization smoke detector? - Correct Answer-A detector that uses a small amount of radioactive material to ionize the air between two differently charge electrodes. When smoke is present between these electrodes, it causes the conductance of the air to decrease, and this causes the alarm to trip. 41.What is a photoelectric light scattering smoke detection? - Correct Answer-A detector that uses light source and a photosensitive sensor, arranged so that light
50.If speakers are used to generate audible fire signals, what rule must apply? - Correct Answer-The speaker must be monitored for integrity. Any failure should result in a trouble signal. 51.In one or two family dwelling, where must smoke detectors be located? - Correct Answer-All sleeping rooms, outside of each sleeping area and on all levels of the dwelling, (including basements) 52.Where must spot type heat and smoke sensors be located on walls and ceilings?
58.Detectors and appliances shall be protected from damage by a mechanical guard as long as? - Correct Answer-It is listed for the purpose and does not interfere with the operation of the device. 59.What is a water flow device? - Correct Answer-An attachment to the sprinkler system that can detect a predetermined rate of water flow, and is able to initiate the fire alarm. 60.When water flow occurs that is equal to or greater than the flow of a single sprinkler, how quickly shall the alarm signal initiate? - Correct Answer- 90 seconds 61.Can detectors be installed within an air duct system? Can they used as a substitute for open area protection? - Correct Answer-Yes and No 62.Detectors shall be ___ for the purpose which they are being used. - Correct Answer-Listed (i.e UL Listed) 63.Which Signals must take priority over all other signals? - Correct Answer-Fire. Even if a non-fire signal is generated first. 64.All extinguishment system with automatic detection equipment for activation shall also have? - Correct Answer-Means for manual activation (pull station) 65.How many fire alarm boxes (pull stations) are required in systems employing automatic fire or water flow detectors? - Correct Answer-At least one, located where required by the authority having jurisdiction.
76.Detectors and appliances can be mounted using wires behind them. True or False - Correct Answer-False. All detectors and appliances must be secured independently of their wiring. 77.Fire alarm pull boxes shall be located where? - Correct Answer-Throughout the protected area, in conspicuous locations. They must be within 5ft of the exit doorway on each floor. 78.Partitions shall cause spaces to be considered separate rooms when they extend to within what %? - Correct Answer- 15 79.Non fire alarm equipment is permitted to be integrated with the fire alarm system so long as? - Correct Answer-Any grounds or short circuits in this equipment do not cause interference with the fire alarm equipment. 80.What is the purpose of an end of line resistor? - Correct Answer-To supervise the current flowing through appliances and detector circuits, so that grounds and faults can be detected. 81.What MUST monitored for integrity? - Correct Answer-The installation wiring between the fire alarm control unit and the relay or other appliance (horn/strobe etc) 82.Each elevator lobby , elevator hoistway and elevator machine room detector MUST be capable of what? - Correct Answer-Initiating elevator recall when all other devices alarm condition. 83.Must the fire alarm devices within the elevator hoist way be integrated with the fire alarm? - Correct Answer-Yes
84.Wall mounted appliances must be located between which two distances above finished floor? - Correct Answer-Not less than 80 inches and not greater than 96 inches above the finished floor. 85.Average ambient sound levels greater than ___ shall require the use of ____? - Correct Answer-95db, Visual notification appliances 86.Any device intended to lock or unlock the exits shall be ______ - Correct Answer-Connected to the fire alarm system 87.When may manual testing be extended to ANNUALLY? - Correct Answer-If automatic testing is performed AT LEAST weekly by a remote fire alarm control unit 88.In a non-house-household applications, when shall the sensitivity of smoke detectors be tested? - Correct Answer-Within one year or installation and alternating years thereafter. However, if the second sensitivity test indicates that the detector has stayed within a healthy range, the time between calibration tests may be extended for up to 5 years. 89.Before proceeding with any testing, who must be notified and why? - Correct Answer-Facilities receiving the alarm and all building occupants. The purpose is to avoid unnecessary response. 90.How long does a monitoring facility have to notify clients of a change in service provider? - Correct Answer-30 days, in writing 91.In areas in which more than two visual notification appliances can be seen, they shall be _______ - Correct Answer-Synchronized. This is to avoid triggering epileptic seizures.
cable, enclosure, cable tray, raceway, or cable routing assembly. - Correct Answer-True