Docsity
Docsity

Prepare for your exams
Prepare for your exams

Study with the several resources on Docsity


Earn points to download
Earn points to download

Earn points by helping other students or get them with a premium plan


Guidelines and tips
Guidelines and tips

KY HVAC JOURNEYMAN EXAM QUESTIONS AND CORRECT ANSWERS ALREADY GRADED A+ 2024 NEWEST UPATE, Exams of Refrigeration and Air Conditioning

KY HVAC JOURNEYMAN EXAM QUESTIONS AND CORRECT ANSWERS ALREADY GRADED A+ 2024 NEWEST UPATE (BRADNEW)

Typology: Exams

2024/2025

Available from 02/01/2025

BESTOFLUCK
BESTOFLUCK 🇺🇸

4.2

(5)

2.1K documents

1 / 27

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
KY HVAC JOURNEYMAN EXAM QUESTIONS AND
CORRECT ANSWERS ALREADY GRADED A+ 2024
NEWEST UPATE (BRADNEW)
Fuel Oil is defined as Kerosene or any hydrocarbon oil having a flash point not less than ____:
a: 150°F
b: 250°F
c: 225°F
d: 100°F
d: 100°F
Refer: IMC Code - Definitions
Automatic operation of the system shall not reduce the ventilation airflow rate below _____ cfm per
square foot of the enclosed parking garage floor area
a: 0.05
b: 0.5
c: 5
d: 50
a: 0.05
Refer: IMC Code 404.2
Ozone cabinets and ozone gas-generator rooms for systems having a maximum ozone generating
capacity of 1/2 pound (0.23 kg) or more over a 24-hour period shall be mechanically ventilated at a rate
of not less than ______ air changes per hour:
a: 5
b: 6
c: 10
d: 12
pf3
pf4
pf5
pf8
pf9
pfa
pfd
pfe
pff
pf12
pf13
pf14
pf15
pf16
pf17
pf18
pf19
pf1a
pf1b

Partial preview of the text

Download KY HVAC JOURNEYMAN EXAM QUESTIONS AND CORRECT ANSWERS ALREADY GRADED A+ 2024 NEWEST UPATE and more Exams Refrigeration and Air Conditioning in PDF only on Docsity!

KY HVAC JOURNEYMAN EXAM QUESTIONS AND

CORRECT ANSWERS ALREADY GRADED A+ 2024

NEWEST UPATE (BRADNEW)

Fuel Oil is defined as Kerosene or any hydrocarbon oil having a flash point not less than ____: a: 150°F b: 250°F c: 225°F d: 100°F  d: 100°FRefer: IMC Code - Definitions Automatic operation of the system shall not reduce the ventilation airflow rate below _____ cfm per square foot of the enclosed parking garage floor area a: 0. b: 0. c: 5 d: 50  a: 0.Refer: IMC Code 404. Ozone cabinets and ozone gas-generator rooms for systems having a maximum ozone generating capacity of 1/2 pound (0.23 kg) or more over a 24-hour period shall be mechanically ventilated at a rate of not less than ______ air changes per hour: a: 5 b: 6 c: 10 d: 12

b: 6Refer: IMC Code 509.9. The PVC duct for domestic kitchen cooking appliances equipped with downdraft exhaust system shall extend not more than _____ above the indoor concrete floor surface: a: 1 inch b: 2 inch c: 1.5 inch d: 2.5 inch  a: 1 inchRefer: IMC Code 505.1 Exp 2. The operating temperature of fire damper actuating device shall be approximately _____ above the normal temperature within the duct system a: 50°F b: 100°F c: 75°F d: 125°F  a: 50°FRefer: IMC Code 607.3.3.1. The pressure classification of ducts shall equal or ______ the design pressure of the air distribution in which the ducts are utilized: a: lower than b: greater than  b: greater thanRefer: IMC Code 603.

Ferrous fan blades shall only be used for fans located within the ductwork and through which hazardous materials are exhausted. False True  FalseRefer: IMC Code 502.9. Intake openings shall be located not less than 3 feet below contaminant sources where such sources are located within _____ of the opening: a: 10 feet b: 12 feet c: 14 feet d: 16 feet  a: 10 feetRefer: IMC Code 401.4. As per Department of Transportation (DOT) specification cylinders with a maximum water capacity of _____ shall be used for completely self-contained hand torches and similar applications a: 2 pounds b: 1.5 pounds c: 5 pounds d: 2.5 pounds  d: 2.5 poundsRefer: IMC Code 502.9.10. Venting systems shall be designed and constructed so as to develop a ______ flow adequate to convey all combustion products to the outside atmosphere: a: either positive or negative

b: negative c: positive  c: positiveRefer: IMC Code 801. Ducts shall be supported with approved hangers at intervals not exceeding _____ : a: 8 feet b: 12 feet c: 14 feet d: 10 feet  d: 10 feetRefer: IMC Code 603. Where the vent vertical termination is located below an adjacent roof structure, the termination point of mechanical draft system shall be located at least _____ from such structure: a: 4 feet b: 6 feet c: 5 feet d: 3 feet  d: 3 feetRefer: IMC Code 804.3.5. Which of the following flammable liquid having a flash point below 73°F (23°C) and a boiling point below 100°F (38°C) a: Class ID b: Class IC c: Class IB

Refer: IMC Code 502.4. The individual modular boiler shall be limited to a maximum input rating of ______ Btulh gas: a: 4,000,00 0 b: 4, c: 400, d: 40,  c: 400,Refer: IMC Code - Definitions Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than _____ in thickness and there are no openings serving the corridor: a: 0.19 inch b: 0.0019 inch c: 1.9 inch d: 0.019 inch  d: 0.019 inchRefer: IMC Code 607.5.4 Exp 3 Exhaust Openings in screens, louvers and grilles terminating at outdoor shall be sized not less than ______ : a: 1/4 inch b: 1/3 inch c: 1/2 inch d: 3/4 inch  a: 1/4 inchRefer: IMC Code 501.3.

Chimney connectors for low-heat appliances shall be of sheet steel pipe having diameter of 7 inches shall have minimum normal thickness of _____ that of galvanized steel: a: No. 22 b: No. 24 c: No. 26 d: No. 30  b: No. 24Refer: IMC Code Table 803.9(1) Where ducts used for cooling are externally insulated, the insulation shall be covered with a vapor retarder having a maximum permeance of ______ perm: a: 0. b: 0. c: 5 d: 0.  a: 0.Refer: IMC Code 604. Commercial kitchen Exhaust outlets that terminate above the roof shall have the discharge opening located not less than _____ above the roof surface: a: 60 inches b: 50 inches c: 25 inches d: 40 inches  d: 40 inchesRefer: IMC Code 506.3.13.

Chimney and vent connectors shall have a minimum clearance of _______ to electric and oil incinerators: a: 9 b: 24 c: 18 d: 36 c: 18 Refer: IMC Code Table 803.10. Ducts that operate at temperatures exceeding ______ shall have sufficient thermal insulation to limit the exposed surface temperature a: 120°F b: 150°F c: 200°F d: 250°F a: 120°F Refer: IMC Code 604. The termination point of all environmental air exhaust outlets and ducts discharging to the outdoors shall be located _____ from property lines: a: 10 feet b: 3 feet c: 6 feet d: 15 feet b: 3 feet Refer: IMC Code 501.3.

Class B Refrigerants shall have toxicity at concentrations below ______ , based on data used to determine TLV-TWA or consistent indices: a: 100 ppm b: 400 ppm c: 1000 ppm d: 200 ppm b: 400 ppm Refer: IMC Code - Definitions Where a damper is installed within a duct, a smoke detector shall be installed in the duct within _____ of the damper with no air outlets or inlets between the detector and the damper: a: 4 feet b: 3 feet c: 5 feet d: 6 feet c: 5 feet Refer: IMC Code 607.5.4.1. Mechanical and gravity outdoor air intake openings shall be located not less than _____ horizontally from any hazardous or noxious contaminant source a: 12 feet b: 16 feet c: 8 feet d: 10 feet d: 10 feet Refer: IMC Code 401.4.

Brainpower Read More Liquids having flash points at or above 100°F (38°C) and below 140°F (60°C) comes under ________ combustible liquid: a: Class I b: Class II c: Class IIIA d: Class IIIB b: Class II Where located adjacent to walkways, the vertical termination of mechanical draft systems shall be not less than ______ above the level of the walkway: a: 7 feet b: 5 feet c: 3 feet d: 4 feet a: 7 feet Refer: IMC Code 804.3.5. Commercial kitchen Grease duct systems serving a Type I hood shall be designed and installed to provide an air velocity within the duct system of not less than ______ feet per minute: a: 1000 b: 500 c: 400 d: 250 b: 500

Refer: IMC Code 506.3. The minimum openable area to the outdoors shall be ____ of the floor area being naturally ventilated: a: 6% b: 8% c: 4% d: 2% c: 4% Refer: IMC Code 504. Fire dampers are not required at penetrations of shafts where the steel exhaust subducts extend at least _______ vertically in exhaust shafts provided that there is a continuous airflow upward to the outdoors: a: 25 inches b: 22 inches c: 32 inches d: 28 inches b: 22 inches Refer: IMC Code 607.5.5 Exp 1. Underground Ducts shall have a minimum slope of _______ per foot to allow drainage to a point provided with access: a: 1/2 inch b: 1/6 inch c: 1/4 inch d: 1/8 inch d: 1/8 inch

Commercial cloth dryer ducts shall have a minimum clearance of _____ to combustible materials: a: 9 inches b: 12 inches c: 8 inches d: 6 inches d: 6 inches Refer: IMC Code 504. The vent horizontal termination point for a mechanical draft system shall not be located closer than _____ to an interior corner formed by two walls perpendicular to each other. a: 5 feet b: 6 feet c: 4 feet d: 3 feet d: 3 feet Refer: IMC Code 804.3.4. Breathing Zone region shall be more than _______ from the walls of the space or from fixed air- conditioning equipment: a: 3 feet b: 1.5 feet c: 2 feet d: 0.5 feet c: 2 feet Refer: IMC Code - Definitions

Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at _____ or less: a: 40% b: 60% c: 50% d: 30% b: 60% Refer: IMC Code 403.2.1. The termination point of exhaust outlets and ducts discharging explosive or flammable vapors, fumes or dusts to the outdoors shall be located with _______ from property lines a: 18 feet b: 24 feet c: 15 feet d: 30 feet d: 30 feet Refer: IMC Code 501.3. Positive mechanical ventilation which provides a minimum of ______ complete air changes per hour shall be installed in limited spraying spaces a: six b: four c: five d: eight a: six Refer: IMC Code 502.7.

Manual dampers shall be installed in connectors except in chimney connectors serving solid fuel-burning appliances: True False False Refer: IMC Code 803. The vent vertical termination for mechanical draft system shall be located at least horizontally _____ from any portion of the roof structure: a: 2 feet b: 3 feet c: 5 feet d: 4 feet b: 3 feet Refer: IMC Code 804.3.5. For duct wrap, the installed thickness of duct insulation used to determine R-value (Thermal Resistance) shall be assumed to be ______ of nominal thickness: a: 25% b: 40% c: 75% d: 50% c: 75% Refer: IMC Code 604.7.

Mechanical ventilation shall be provided at a rate of not less than _____ cfm per square foot of floor area over the storage area: a: 2 b: 1. c: 2. d: 1 d: 1 Refer: IMC Code 502.8.1.1. Cleanouts serving horizontal sections of grease ducts shall be located not more than _____ from changes in direction that are greater than 45 degrees: a: 8 feet b: 12 feet c: 6 feet d: 10 feet d: 10 feet Refer: IMC Code 506.3.9. The cross-sectional area of a flue serving a solid-fuel-burning appliance shall be not greater than ______ times the cross-sectional area of the appliance flue collar or flue outlet: a: 2 b: 5 c: 4 d: 3 d: 3 Refer: IMC Code 801.