









Study with the several resources on Docsity
Earn points by helping other students or get them with a premium plan
Prepare for your exams
Study with the several resources on Docsity
Earn points to download
Earn points by helping other students or get them with a premium plan
Community
Ask the community for help and clear up your study doubts
Discover the best universities in your country according to Docsity users
Free resources
Download our free guides on studying techniques, anxiety management strategies, and thesis advice from Docsity tutors
Power equation - ✔✔P=IV; power (watts)=current (amps) x voltage (volts) Power equation three phase - ✔✔Power=Voltage (v) x Current (I) x 1.73 x Power Factor (PF) If operating reserve gradually decreases throughout the hour, it's because . - ✔✔Incorrect load forecast Operating reserves are made up of and . - ✔✔Regulating Reserves and Contingency Reserve What type of reserves are used for AGC? - ✔✔Regulating A BA's MSSC is usually its . - ✔✔Largest Generator Equation to determine speed in RPM of a Generator? - ✔✔7200/# of poles At what frequency will a generator trip on underfrequency? - ✔✔57.5 Hz Why do we have underfrequency tripping? - ✔✔Protect turbines from damage
Typology: Exams
1 / 17
This page cannot be seen from the preview
Don't miss anything!
Power equation - ✔✔P=IV; power (watts)=current (amps) x voltage (volts) Power equation three phase - ✔✔Power=Voltage (v) x Current (I) x 1.73 x Power Factor (PF) If operating reserve gradually decreases throughout the hour, it's because. - ✔✔Incorrect load forecast Operating reserves are made up of and. - ✔✔Regulating Reserves and Contingency Reserve What type of reserves are used for AGC? - ✔✔Regulating A BA's MSSC is usually its. - ✔✔Largest Generator Equation to determine speed in RPM of a Generator? - ✔✔7200/# of poles At what frequency will a generator trip on underfrequency? - ✔✔57.5 Hz Why do we have underfrequency tripping? - ✔✔Protect turbines from damage Why does frequency drop faster/is harder to correct, when we have a disturbance when we have increased wind generation? - ✔✔Less inertia/governor response to correct frequency Frequency above 60 Hz means. - ✔✔Overgenerating Frequency below 60 Hz means. - ✔✔Undergenerating
Frequency decrease is usually caused by. - ✔✔Loss of generation A 1% drop in frequency results in. - ✔✔2% drop in total load; 3% drop in motor load Formula for ACE? - ✔✔NIa-NIs - 10B(Fa-Fs) Governor response is based on its characteristic. - ✔✔Droop 5% of 60 Hz= - ✔✔ 3 Hz; most Governor's have 5% droop characteristic Droop setting is the % required for a generator to run at capacity. - ✔✔Full What is the purpose of a governor deadband? - ✔✔Minimize wear on equipment What % for governor deadband? - ✔✔+/- .036 Hz An isochrynous generator setting has droop. - ✔✔0% When are isochryonous generators used? - ✔✔one unit, during islanding Is 10% droop or 5% droop more responsive? - ✔✔5% On a classic disturbance chart, what brings frequency from point c to d? - ✔✔Contingency Reserve On a classic disturbance chart, what causes a 'step' change? - ✔✔Fast-start generator What's the primary response to frequency drop? - ✔✔Governor response
BA has to recover its ACE back to ____f it was positive or zero before a disturbance. - ✔✔ 0 BA has to recover its ACE back to if it was negative before a disturbance. - ✔✔pre-disturbance value BAL- 003 says each BA shall implement settings. - ✔✔Frequency Bias If B=frequency response, ACE is--------- ✔✔unchanged If B is more negative than actual frequency response, ACE is and units on AGC will. - ✔✔negative; increase output If B is less negative than actual frequency response, ACE is and units on AGC will--------- ✔✔positive; hurt frequency BAL- 005 says BA has to scan ACE every -------- ✔✔six seconds BAs must notify RC if unable to calculate ACE for more than --------- ✔✔ 30 minutes helps maintain ACE by adjusting resources. - ✔✔AGC (Automatic Generation Control) AGC should always operate in what mode? - ✔✔Tie-Line Bias What AGC mode should be used when restoring an island? - ✔✔Flat frequency To fix a fast time error, Frequency should be set to ___. - ✔✔59. To fix a slow time error, Frequency should be set to. - ✔✔60.
Formula to calculate Inadvertent Interchange? - ✔✔NIa-Nis INT-006 says has to be assessed for reliability before implementation. - ✔✔Interchange Source or Sink BA must interchange if it does not expect to be capable of supporting the magnitude, ramping, or scheduling path. - ✔✔Deny Only and can approve Interchange Tags. - ✔✔BAs and TSPs When are Interchange transactions implemented? - ✔✔When entered into the ACE equation Who confirms Tags? - ✔✔Sink BA What part of ACE do Dynamic Schedules impact? - ✔✔NIs What part of ACE do Psuedo Ties impact? - ✔✔NIa Dynamic transfers are used for. - ✔✔JOGs (jointly owned generators) Indication of loss of load could be caused by error. - ✔✔Generator/Meter When you lose a block of load, NIa and ACE. - ✔✔increases; increases When you lose a generator, NIa and ACE. - ✔✔decreases; decreases Formula for system load? - ✔✔Total generation - Net actual interchange When a generator is lost outside of your BA, ACE and frequency. - ✔✔stays the same; drops
provide reactive power close to where it is needed. - ✔✔Shunt Capacitors absorb excess VARs. - ✔✔Shunt Reactors Generator is underexcited and leading when it is MVARs. - ✔✔Absorbing Generator is overexcited and lagging when it is MVARs. - ✔✔Delivering/adding During restoration, you want your generator to be leading or lagging? - ✔✔Leading Generator capability limit is based on limits. - ✔✔Thermal produce only reactive power (when generator is in condenser mode); Basically, a generator without a prime mover. - ✔✔Synchronous Condensers is a capacitor and a reactor combo that provides dynamic reactive resources. - ✔✔SVC (Static Var Compensator) What device moves MVARs by changing the ratio of windings? - ✔✔Under Load Tap Changer are not reactive resources; they effectively lengthen or shorten the transmission line. - ✔✔Series capacitors and Series reactors Where are shunt capacitors placed? - ✔✔Close to inductive load To get ahead of voltage, system operators should do what? - ✔✔Put capacitors into service prior to peak
Formula for MVAR output? - ✔✔MVAR output=MVAR rated x (Voltage Actual/Voltage Rated)² Shunt Reactors are located near. - ✔✔High voltage stations What is used to reduce voltage by absorbing MVARs? - ✔✔Shunt Reactors What is used to increase voltage by adding MVARs? - ✔✔Shunt Capacitors VAR: 002 says GOPs shall operate Generator in mode. - ✔✔AVR (Automatic Voltage Regulator) If a GOP can't operate in AVR mode, they must notify within. - ✔✔TOP; 30 minutes VAR: 001 says must maintain voltage and reactive control. - ✔✔TOP MVAR flow from to voltage. - ✔✔High to low Real power flows from to power angle. - ✔✔Higher to lower Phase Shifting Transformers (PSTs) allow us to change by changing the power angle. - ✔✔Real power flow Formula for Power Losses - ✔✔PL=I²R What happens to power losses when current doubles? - ✔✔Quadruples is when MVAR supplied = MVAR absorbed. - ✔✔SIL (Surge Impedence Loading) P-V curve is used to determine what? - ✔✔Point of system instability because of voltage collapse
What relay usually clears a line-to-ground fault? - ✔✔50 Instantaneous Overcurrent or 51 Timed Overcurrent What relay usually clears a line-to-line fault? - ✔✔ 21 Distance Relay A difference of current in and current out will initiate a relay. - ✔✔ 87 Differential PTs provide indication. - ✔✔voltage CTs provide indication. - ✔✔current Formula for Ohm's Law - ✔✔V=I x R (voltage (volts)=current (amps) x Resistance (Ohms) What relay senses a line's impedance by sensing current and voltage from CTs and PTs? - ✔✔ 21 - Distance Relay Zones of Protection for Distance Relay--What % for Zone 1, 2, 3? - ✔✔90%, 120%, 200% Sync-check relay automatically closes when phase angle is within. - ✔✔ 30 degrees What detects predetermined system conditions and takes automatic corrective actions to ensure reliability? - ✔✔RAS (Remedial Action Scheme) What can be done to prevent system protection failures? - ✔✔Redundancy, backup protection, overlapping zones, breaker failure protection Lightly loaded transmission lines are. - ✔✔Capacitive/supply MVAR Heavily loaded transmission lines are. - ✔✔Inductive/absorb MVAR
COM- 001 says System Operators must test their alternative communication capability how often? - ✔✔once per calendar month If alternative communications capability test is unsuccessful, how long to repair or replace? - ✔✔ 2 hours When there is a failure with primary communication that lasts 30+ minutes, must notify affected entities within. - ✔✔60 minutes COM- 002 says all Operating Instructions must. - ✔✔follow documented protocols How often must Comm Protocols be assessed? - ✔✔Once every 12 months A command by operating personnel for real time ops? - ✔✔Operating Instruction What is an RTU? - ✔✔Remote Terminal Unit; found in field substations; 2 - way communication device from control room to field Supervisory Control and Data Acquisition - ✔✔SCADA Inter-control Center Communication Protocol - ✔✔ICCP Reliability Coordinator Information System - ✔✔RCIS If you are the RC and ICCP goes down, what do you do? - ✔✔Implement Backup functionality plan Where do RCs post messages and share operating info occurring in real time? - ✔✔RCIS
SOL are determined by the most limit. - ✔✔Restrictive is an SOL that could cause instability, cascading, etc. - ✔✔IROL What is the maximum time an IROL can be violated? - ✔✔Tv (30 minutes max) Contingency Analysis tools include: - ✔✔State Estimator, CA, CM What tool simulates power flow for a set of contingencies? - ✔✔Contingency Analysis What tool is used by RCs to determine contribution to flowgate loading? - ✔✔Congestion Management What is the IDC (interchange distribution calculator) used for? - ✔✔Congestion Management One must comply with Operating Instructions unless. - ✔✔It would violate safety, equipment, or Regulatory/Statutory regulations Shift factor that tells % change in loading due to power transfer (interchange)? - ✔✔PTDF Shift factor that tells % a change in generator will impact a transmission facility. - ✔✔GSF What formula is used to determine relief on a line? - ✔✔Overload/Distribution Factor A positive GSF means generation. - ✔✔decrease A negative GSF means generation. - ✔✔increase
With 2 positive GSFs, always the generator with the lower shift factor and the generator with the higher shift factor. - ✔✔increase; decrease Who issues TLRs (Transmission Loading Relief)? - ✔✔RC RC has to perform real time assessment how often? - ✔✔every 30 minutes Who has to develop operating plans for emergencies? - ✔✔BA and TOP Who must coordinate actions during an emergency? - ✔✔RC Who must be notified by TOP in an emergency? - ✔✔RC, impacted TOPs and BAs Who deals with capacity and energy emergencies? - ✔✔BA In extreme cold weather, the RC would be concerned about. - ✔✔fuel shortages (natural gas) What level EEA? All available resources are in use. - ✔✔EEA 1 What level EEA? Load management procedures are in effect. - ✔✔EEA 2 What level EEA? Firm load interruption is immiment/in progress - ✔✔EEA 3 Who issues EEAs? - ✔✔RC How long do RCs have to notify other BAs and TOPs (as well as neighboring RCs) of an emergency request notification? - ✔✔30 minutes During EEA 2, the BA can still meet its requirements. - ✔✔Contingency Reserve
What are the three Rs of Emergency Response? - ✔✔Redispatch, Reconfigure, Reduce Generator that can start without system support? - ✔✔Blackstart, usually CT or hydro What are cranking paths? - ✔✔Paths used to start up other generating units during restoration First priority in restoration is to restore power where? - ✔✔Off-site nuclear/critical facilities What kind of lines make the best cranking paths? - ✔✔Shorter lines, overhead What is an increase in load magnitude when a feeder is re-energized following an outage period? - ✔✔Cold load pickup Instantaneous electric current drawn by a motor in the fractions of a second after a motor turns on? - ✔✔Motor in-rush current (10x normal) What are the primary causes of cold load pickup? - ✔✔Motor in-rush current and Load Diversity Anything with a thermostat or load cycles creates. - ✔✔Load diversity What are the two strategies for restoration? - ✔✔Open all breakers, Controlled Breaker Biggest disadvantage of opening all breakers during restoration? - ✔✔Limited battery resources could be depleted will be more erratic during restoration. - ✔✔Frequency (maintain 59.75- 61 Hz) Shed % of load in order to raise frequency by 1 Hz. - ✔✔ 6 - 10%
Load blocks should be restored in increments of % of total connected load. - ✔✔5% Who has to have Restoration Coordination plans? - ✔✔RCs EOP-005 says must have Restoration Plans. - ✔✔TOPs Who has to review the TOPs' Restoration plans? - ✔✔RC TOPs must verify their restoration plans every through simulation. - ✔✔ 5 years How often must Blackstart units be tested? - ✔✔every 3 years What is the voltage range during restoration? - ✔✔± 10% of nominal How often must TOPs evaluate their Restoration Plans? - ✔✔annually TOPs must provide field switching personnel with ___ system restoration training each year. - ✔✔ 2 hours EOP-006 says RCs must conduct restoration drills per year? - ✔✔ 2 RCs are responsible for during restoration. - ✔✔Coordination When does an RC's Restoration Coordination plan start and end? - ✔✔When blackstart units are used until all TOPs are interconnected and its RC area is connected to neighboring RC areas A 5% decrease in voltage results in % decrease in load. - ✔✔3%