A comprehensive set of questions and answers related to the nicet level 2 exam for the itm of water based systems. It covers various aspects of fire sprinkler systems, including maintenance, testing, and inspection procedures. Useful for individuals preparing for the nicet level 2 exam and those involved in the installation, maintenance, and inspection of fire sprinkler systems.
Typology: Exams
1 / 7
This page cannot be seen from the preview
Don't miss anything!
When is it necessary to conduct a Main Drain Test? annually or any time the water supply control valve is closed, this includes any time a fire sprinkler system undergoes maintenance or repair. What document is needed to determine whether there has been a 10%reduction in full flow pressure in the water supply , in relation to the results of the current main drain test? Original acceptance test reports or previous test What is the most common use for a Hydropneumatic Machine/pump? For Internal Pipe Obstruction Flushing/ 5 year flushing Before servicing a dry system air compressor, what device can be used to safely determine that power is not being supplied to the compressor? Voltage Meter According to NFPA 25, What is the typical size of an impairment tag? 4in x 6in
The Hydraulic design information sign for a standpipe system, when provided, shall be at what interval in order to verify that it is attached and is legible? Annualy Obstruction investigations should be recommended when what situations occur? After extended period of being shut down and returned to service, drains or inspectors test plugged by foreign material, and/or obstructive material observed during drain test When preforming a churn test (no flow condition) on a Diesel Fire Pump, what is the minimum run time? 30 Minutes How frequently shall a Vane Type water flow switch be tested? Semi-Annually To prevent jammin, what shall be done to post indicator and OS&Y Valves? Backed 1/4 turn from the fully open position When Annually testing a fire hydrant, what is the minimum flow time according to NFPA 25? 1 minute Which agency should be contacted in order to determine whether a tamper/supervisory signal was received during the semi-annual test of a wet system control valve? Central Monitoring Station
What course of action is required when testing fast response type sprinklers that have been in service for 20 years? replaced or representative samples shall be tested and the retested at 10 year intervals How often are monitor nozzles to be inspected? semi-annually Who is responsible for maintaining all sprinkler system reports? Building/property Owner How frequently shall the interior of a dry pipe valve be inspected? Annually when the trip test is conducted According to NFPA 25, what is determined through inspection and periodic testing of water-based fire systems? Action needed to fix what has been changed An antifreeze loop has a capacity of 350 gallons. How many points should it be tested at? 4, Both most remote point and where the system meets with the water supply. Also, where antifreeze systems have a capacity lager than 150 gal, test at one additional point for every 100 gal shall be made. During a planned system impairment, where should the impairment tag be posted?
The system control valve While preforming the third year air leakage test on a dry system, it is noticed that there was a loss of pressure in the 2-hour time period. According tp NFPA 25, what is the maximum loss (in psi) allowed? 3 psi How frequently should the main drain test be run on pressure reducing valves and backflow preventors installed and acting as the sole source of the water supply? Quarterly What is the time interval for the internal inspection of non-metallic pipe? Not required for nonmetallic pipe At what elevation shall the test pressure be measured while preforming a hydrostatic test on a manual dry standpipe? The lowest elevation point in the system How often are pressure gauges on a pre action system required to be tested or replaced? Every 5 years or as needed A Water tank with NO low temperature alarm is connected to a constantly monitored location. When conditions are below 40 F, how often must the temperature of the water in the tank be inspected and recorded? Weekly
Quarterly What type of system will transmit alarm, supervisory, and trouble signals from one or more protected premises to a remote location where appropriate action is taken? Remote Supervising Station Alarm System What can be used to preform the full flow test of a back flow valve? Test header What two tools can be used to check the status of a supervisory switch? Amp Probe and a voltmeter what is the nominal breaking strength of safety belt lanyard material? 5,400 pounds