identifying what air handling unit to use
Typology: Cheat Sheet
1 / 15
This page cannot be seen from the preview
Don't miss anything!
Marriot North Wing Hotel-Level 9
(Grand Corridor, Lift Lobbies)
Quiz 4
Rabang, Jan Marcel, C.
Engr. Renato Afurong
Instructor
January 14, 2023
Requirements:
A. Air conditioning Load Estimate
1 Student Report
B. Supply air duct design using equal friction method
C. Equipment Selection
a. Estimated capacity of chiller (water cooled)
b. Chiller Data Selected
c. Chilled and cooling water flow in gpm
d. Schematic diagram showing the chiller, cooling towe, cooling &chilled water pumps,
flow rate in gpm, entering/leaving temperatures and pressure drops on the chiller &
condenser.
e. High-lighted selected data on the brochure
f. Specification of the chiller
a. AHU Tabulated Data
b. AHU Data Selected
c. Chilled and cooling water flow in gpm
d. Schematic diagram of AHUs
e. Highlighted selected data of the brochure
f. Specification of AHUs
D. Economics- Comparison of Air-cooled & Water-cooled chiller
Orientation:
76 FDB 50% RH
96 FDB 80 FWB
2966.16 cfm
525.36 cfm
700.476 cfm
1105.75 cfm
1686.14 cfm
2266.53 cfm
2966.16 cfm
Total cfm = 2966.16 cfm
ଶ
Selected duct size = 18 in * 18 in
Equivalent round duct diameter = 19.7 in
0.15 in W.G/100 ft. length of duct
2966.16 cfm
1500 fpm
AREA (sq. ft.) DUCT SIZE
(in.)
AHU to A 2966.16 100 100 1.98 18 x 18
A- 2 2266.53 76 81 1.6038 18 x 14
2 - 3 1686.14 57 65 1.28 14 x 14
3 - 4 1105.75 37 45 0.891 12 x 12
A- 1 700.476 24 31.5 0.6237 10 x 10
4 - 5 525.36 18 25 0.495 10 x 8
Duct Section Item Length (ft) Additional Equivalent Length (ft)
AHU – A Duct 6.5 6
--- Elbow 13
A- 2 Duct 61.
2 - 3 Duct 61.
3 - 4 Duct 61.
4 - 5 Duct 28.
--- Elbow 6
Total 218. 49 19
Longest Run Air Distribution
Computation for Diffuser Sizes:
ௗ௨௦