Guidelines for maintaining and inspecting citywide sprinkler systems. It includes information on responsibilities of building owners, record-keeping, planned and unplanned removal from service, tagging, impairment coordination, and system protection. It also covers topics such as exterior exposure sprinklers, foam supply systems, and fire pumps. useful for those studying fire protection engineering or building management.

Typology: Exams

2022/2023

Available from 11/11/2023

johnNice
johnNice šŸ‡ŗšŸ‡ø

541 documents

1 / 20

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
S-12 CITYWIDE SPRINKLER SYSTEMS, S12
sprinkler test Spring Latest Update
2023.Assured Success..
1. THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS. - answers>OWNER
2. RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF
__________ YEARS. - answers>3
3. THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH REQUIREMENTS. -
answers>IMPAIRMENT COORDINATOR
4. REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE
CONSIDERED PLANNED REMOVAL FROM SERVICE. - answers>1
5. SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED OUT
OF SERVICE CONDITIONS. - answers>1
6. NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN
______ HOURS. - answers>8
7. FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT
CONDITION TO THE ___________ AND THE FIRE DEPT. - answers>OWNER OF THE BUILDING
8. IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT WILL
BE CONSIDERED AN IMPAIRMENT. - answers>30
9. WHAT DOES "OOS" STAND FOR? - answers>OUT OF SERVICE
10. OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS, SYS.
CONTROL VALVES, AND FIRE COMMAND CENTER - answers>TAGS
pg. 1
pf3
pf4
pf5
pf8
pf9
pfa
pfd
pfe
pff
pf12
pf13
pf14

Partial preview of the text

Download Citywide Sprinkler Systems Maintenance and Inspection Guidelines and more Exams Nursing in PDF only on Docsity!

S-12 CITYWIDE SPRINKLER SYSTEMS, S

sprinkler test Spring Latest Update

2023.Assured Success..

1. THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE

QUALIFICATIONS. - answers> OWNER

  1. RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF __________ YEARS. - answers> 3
  2. THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH REQUIREMENTS. - answers> IMPAIRMENT COORDINATOR
  3. REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - answers> 1
  4. SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS. - answers> 1
  5. NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN ______ HOURS. - answers> 8
  6. FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. - answers> OWNER OF THE BUILDING
  7. IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - answers> 30
  8. WHAT DOES "OOS" STAND FOR? - answers> OUT OF SERVICE
  9. OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - answers> TAGS

11. A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY SECTIONAL

VALVES. - answers> MASTER FIRE SUPPRESSION PIPING CONTRACTOR

  1. __________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER. - answers> DRAIN TEST RESULTS
  2. GREEN TAGS INDICATE THAT __________. - answers> NO IMPAIRMENT WAS FOUND
  3. GREEN TAGS WILL BE PLACED ON THE ____________. - answers> MAIN CONTROL VALVE
  4. SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG PLACED ON THE MAIN CONTROL VALVE. - answers> RED
  5. A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - answers> WHITE
  6. A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - answers> BLUE
  7. THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL STATION AND OCCUPANTS. - answers> INSURANCE
  8. PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - answers> IMPAIRMENT COORDINATOR
  9. GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - answers> 50, 40
  10. THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE ____________. - answers> MAIN CONTROL VALVE
  1. DRY PIPE VALVES ARE OF A ______ DESIGN. - answers> CLAPPER
  2. DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL TRIP LEVEL. - answers> 15-
  3. AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME TO ALLOW WATER INTO THE SYSTEM. - answers> REDUCE
  4. BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP OF _______ PSI IS DETECTED IN THE SYSTEM. - answers> 2
  5. IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE SPRINKLER HEADS. - answers> PREACTION VALVE
  6. PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS OPENED. - answers> VALVE
  7. THREE DEVICES USED TO TRIP PREACTION VALVES ARE FIXED TEMP DEVICES, RATE DEVICES, AND ___________ DEVICES. - answers> COMBINATION
  8. THE _________ FEATURE SHUTS OFF WATER WHEN THE FIRE IS EXTINGUISHED AND TURNS ON AGAIN IF THE FIRE REKINDLES. - answers> RECYCLING
  9. THE ________ IN THE DELUGE SYSTEM ARE OPEN AT ALL TIMES. - answers> SPRINKLER HEADS
  10. _________ SYSTEMS ARE USUALLY FOUND IN BASEMENTS OR OTHER DIFFICULT TO REACH AREAS. - answers> PERFORATED PIPE
  11. ________ NOZZLES ARE USED FOR TRANSFORMER VAULTS AND OTHER HAZARDOUS AREAS. - answers> OPEN-FIXED

44. EXTERIOR EXPOSURE SPRINKLERS USE OPEN SPRINKLER HEADS TO FORM A _______ ON THE

WALL OF A BUILDING. - answers> WATER CURTAIN

  1. _________ SYSTEMS ARE USED FOR THE PROTECTION OF SPECIAL HAZARDOUS OCCUPANCIES. - answers> FOAM SUPPLY
  2. THE COF HOLDER SHALL KNOW THE LOCATION OF ALL SPRINKLER HEADS, CONTROL VALVES, SUPPLY LINES AND _________ ROOMS. - answers> COMPACTOR
  3. A SIGN INDICATING THE LOCATION OF ALL _______ SHALL BE KEPT IN THE COMPACTOR ROOM. - answers> CONTROL VALVES
  4. ALL INDICATING VALVES IN THE COMPACTOR SPRINKLER SYSTEM SHALL BE ________ OPEN. - answers> SEALED
  5. A MINIMUM OF _________ EXTRA SPRINKLER HEADS WITH THE APPROPRIATE WRENCHES SHALL BE AVAILABLE TO REPLACED DAMAGED ONES - answers> 6
  6. THE COF HOLDER SHALL CONDUCT AN INSPECTION OF THE ENTIRE SPRINKLER SYSTEM AT LEAST __________. - answers> ONCE A MONTH
  7. AUTOMATIC BALL DRIP DEVICES SHALL BE INSTALLED IN THE _________ POSITION. - answers> HORIZONTAL
  8. IF THE SPRINKLER SYS. IS SUPPLIED FROM PUBLIC WATER MAIN, THE CONTROL VALVE SIGN MAY READ ________________. - answers> "SHUTOFF FOR SPRINKLER SYS. LOCATED 6 FEET FROM THIS SIGN"
  9. GATE VALVES OF THE NON-INDICATING TYPE ARE CALLED ________. - answers> CURB VALVES
  10. IN AN OUTSIDE STEM AND YOLK VALVE (OS&Y), VALVE POSITION IS INDICATED BY THE POSITION OF THE ____________. - answers> STEM

66. SPRINKLERS MANUFACTURED AFTER 1/1/2000 ARE REQUIRED TO HAVE A _____________. -

answers> SPRINKLER IDENTIFICATION NUMBER (SIN)

  1. _________ SPRINKLERS HAVE BEEN RECALLED. - answers> CYCLING
  2. SPRINKLER HEADS EXPOSED TO ___________ CONDITIONS ARE OFTEN COVERED WITH A COAT OF WAX, OR LEAD. - answers> CORROSIVE
  3. AT A DISTANCE OF 4 FEET BELOW THE DEFLECTOR, THE SPRAY PATTERN COVERS A DIAMETER OF _________ FEET WHEN DISCHARGING AT 15 GPM. - answers> 16
  4. LARGE DROP SPRINKLER HEADS ARE USED TO BREAK THROUGH THE STRONG __________ OF HIGH CHALLENGE FIRES. - answers> UPDRAFTS
  5. IF A FIRE HAS BEEN COMPLETELY EXTINGUISHED, THE __________ OR THEIR REPRESENTATIVE MAY CLOSE THE CONTROL VALVE. - answers> BUILDING OWNER
  6. BUILD UP OF FOREIGN MATERIALS ON SPRINKLER HEADS IS COMMONLY CALLED _________. - answers> LOADING
  7. SPARE SPRINKLERS SHALL BE KEPT AT THE FACILITY WHEN THE TEMPERATURE DOES NOT EXCEED _________. - answers> 100 DEGREES FAHRENHEIT
  8. FACILITIES WITH LESS THAN 300 SPRINKLERS REQUIRE __________ SPARES TO BE AVAILABLE. - answers> 6
  9. FACILITIES WITH 301-1000 SPRINKLERS REQUIRE ________ SPARES TO BE AVAILABLE. - answers> 12
  10. FACILITIES WITH OVER 1000 SPRINKLERS REQUIRE ________ SPARES TO BE AVAILABLE. - answers> 24
  1. PRESSURE TANK TEMPERATURES SHALL BE KEPT AT OR ABOVE _________. - answers> 40 DEGREES FAHRENHEIT
  2. THE MAXIMUM GROSS CAPACITY OF PRESSURE TANKS IS _________ GALLONS. - answers> 9000
  3. PRIMARY WATER PRESSURE TANKS SHALL BE EQUIPPED WITH TWO _____________. - answers> HIGH AND LOW ALARM SYSTEMS
  4. PRESSURE TANKS MAY BE SUPERVISED BY AN APPROVED ________ COMPANY WHICH MONITORS THE ENTIRE SPRINKLER SYSTEM. - answers> CENTRAL STATION
  5. __________ TANKS ARE MADE OF WOOD, STEEL, OR CONCRETE. - answers> GRAVITY
  6. GRAVITY TANKS SHOULD BE AT LEAST ________ FEET ABOVE THE HIGHEST LINE OF SPRINKLER HEADS. - answers> 25
  7. FOR EVERY 1 FOOT THE TANK IS ABOVE THE DISCHARGE OUTLET ___________ PSI OF PRESSURE IS GENERATED. - answers> 0.
  8. AUTOMATIC FILL PUMPS FILL THE TANK AT A RATE OF _________ GPM OR MORE. - answers> 65
  9. THE _______ TURN ON THE FILL PUMP WHEN THE WATER IN THE TANK IS TOO LOW. - answers> FLOATS
  10. SOME METHODS TO PREVENT ICE INSIDE A GRAVITY TANK ARE _________. - answers> CIRCULATED HOT WATER, STEAM, STEAM COILS, AND SUN HEAT
  11. THE MAIN REASON A SPRINKLER SYS. SUPPLIED BY A GRAVITY TANK FAILS IS __________. - answers> NOT ENOUGH WATER IN THE TANK
  12. THE __________ PUMP IS THE STANDARD PUMP CURRENTLY USED IN FIRE PROTECTION SYSTEMS. - answers> CENTRIFUGAL

100. __________ SHALL NOT BE USED TO FASTEN THE SYSTEM OR BUILDING ATTACHMENTS

TO THE STRUCTURE. - answers> NAILS

  1. VISUAL INSPECTION OF HANGING AND BRACING IS NOT REQUIRED FOR PIPING CONCEALED ABOVE __________. - answers> CEILINGS
  2. ____________ LINES ARE DIRECTLY CONNECTED TO SPRINKLER HEADS. - answers> BRANCH
  3. _________ ARE ABLE TO SUPPLY FEED MAINS OR CROSS MAINS DIRECTLY. - answers> RISERS
  4. STANDARD STEEL PIPE WITH DIAMETERS OF 1-1/4 INCH REQUIRE HANGERS TO BE PLACED __________ FEET APART. - answers> 12
  5. FOR PIPE OTHER THAN 1-1/4, THE MAXIMUM DISTANCE BETWEEN HANGERS IS __________ FEET. - answers> 15
  6. CPVC PIPE HANGER SPACE FOR 3/4 INCH PIPE IS ___________. - answers> 5 FT 6 IN
  7. CPVC PIPE HANGER SPACE FOR 3 INCH PIPE IS ________ FEET. - answers> 10
  8. THE DISTANCE FROM A HANGER ASSEMBLY TO THE CENTERLINE OF A SPRINKLER HEAD SHALL NOT BE LESS THAN __________. - answers> 3 INCHES
  9. SYSTEMS ABOVE _________ PSI HAVE DIFFERENT SUPPORT REQUIREMENTS. - answers> 100
  10. NYC BUILDING CODE REQUIRES SWAY BRACING FOR SPRINKLER SYS. INSTALLED AFTER __________. - answers> 1998

111. MINIMUM SIZE HANGER RODS FOR PIPE DIAMETER UP TO 4 INCHES: ___________. -

answers> 3/

  1. MINIMUM SIZE HANGER RODS FOR PIPE DIAMETER OF 5-8 INCHES: ____________. - answers> 1/
  2. MINIMUM SIZE HANGER RODS FOR PIPE DIAMETER OF 10-12 INCHES: ___________. - answers> 5/
  3. THE INSIDE OF PRESSURE TANKS SHALL BE INSPECTED CAREFULLY EVERY _________ YEARS. - answers> 3
  4. WHEN INSPECTING PRESSURE TANKS, THE COMPRESSOR SHALL BE CAPABLE OF PRESSURIZING TO _________ PSI WITHIN 3 HOURS OR LESS. - answers> 75
  5. PUMPS SHOULD BE ACTIVATED EACH WEEK AND RUN FOR _______ MINUTES IN ACCORDANCE TO THE MANUFACTURERS SPECIFICATIONS. - answers> 10
  6. INSTALLATIONS THAT DON'T APPEAR CORRECT INCLUDE SPRINKLER HEADS LOCATED MORE THAN _________ INCHES BELOW THE CEILING. - answers> 22
  7. THE PRESENCE OF OBSTRUCTIONS IN SPRINKLER SYSTEMS SHALL BE CHECKED EVERY _________ YEARS. - answers> FIVE
  8. WHEN TUBERCULES AND SLIME ARE FOUND THEY SHALL BE TESTED FOR ___________. - answers> MICROBIOLOGICALLY INFLUENCED CORROSION
  9. fire department connection - answers> normally on exterior of building... FDNY can pump supplemental water into the sprinkler system, standpipe, or other system furnishing water for fire extinguishment to supplement existing water supplies.
  10. system control valve - answers> valve controlling flow to water-based fire protection systems.
  1. Early suppresion fast response sprinklers - answers> fast response sprinkler that is listed for its capability to provide fire suppression of specific high challenge fire hazards
  2. extra large orifice sprinklers - answers> = or > 1 inch less pressure to achieve a given discharge density
  3. extended coverage sprinkler - answers> 400 max square feet discharge 20 foot by 20 foot spacing between sprinklers
  4. fire pump - answers> a provider of liquid flow and pressure dedicated to fire protection. A fire pump is a part of a fire sprinklers system water supply and can be powered by electric, diesel or steam. connected to public water source or tank. provides higher pressure to sprinkler system
  5. Glass bulb sprinkler - answers> operated by heat breaking a glass bulb filled with a non freezing liquid with diameters that vary form 3 mm for quick response to 5 mm for standard response
  6. hose valve - answers> valve to additional hose connection
  7. hydraulic placard - answers> sign attached to a hydraulically calculated sprinkler system indicating the design density, required gallons per minute and pressure for the system to operate properly
  8. hydraulically calculated systems - answers> method of sizing auto sprinkler piping using a prescribed amount of water to be distributed over a specific area.
  9. impairment coordinator - answers> in charge of safety during out of service systems
  10. intermediate level sprinkler - answers> sprinkler equipped with integral shields to protect the operating elemtn form discharge from sprinklers installed at higher elevations
  1. large orifice sprinkler - answers> sprinkler head with orifice size equal or greater than 3/4 and less than 1 inch
  2. listed device - answers> A fire protection component that has been tested to perform under parameters specified for its use by a nationally recognized testing agency. Underwriter's Laboratory (UL) and Factory Mutual (FM) are the two most common.
  3. Master Pressure Reducing Valve - answers> A pressure reducing valve installed to regulate pressures in an entire fire protection system and/or standpipe system zone.
  4. Main Drain - answers> The primary drain connection located on the system riser and also utilized as a flow test connection.
  5. Microbiologically Influenced Corrosion (MIC) - answers> Corrosion caused by the presence of microbes in the water supply that over time attack the interior of metallic piping and cause leaks, pitting, and blockages.
  6. Conventional Sprinkler - answers> A sprinkler that directs 40% to 60% of the water initially in a downward direction and is designed to be installed with the deflector in either the upright or pendent position.
  7. Pendent Sprinkler - answers> A sprinkler designed to be installed in such a way that the water stream is directed downward against the deflector.
  8. Pintle Screws - answers> A visual indicating device required for sprinklers manufactured prior to 1999 identifying small orifice sprinklers and large orifice sprinklers where orifice size is different than the nominal thread size of the sprinkler head.
  9. Pipe Schedule Systems - answers> A method of sizing piping based upon the number of sprinkler heads and the occupancy of the protected area.
  10. Preaction Sprinkler System - answers> A sprinkler system employing automatic sprinklers that are attached to a piping system that contains air that may or may not be under pressure, with a supplemental detection system installed in the same areas as the sprinklers.
  1. Solder Link Sprinkler - answers> A sprinkler operated by the melting of a metal link, they vary in size and configuration for quick response and standard response sprinklers. The smaller the size of the link, the faster the sprinkler operates.
  2. Spray Sprinkler - answers> A type of sprinkler listed for its capability to provide fire control for a wide range of fire hazards. The most commonly used sprinkler since 1953.
  3. Standard Response Sprinkler Head - answers> A sprinkler having a fusible link with a response time index (RTI) of 80 or more.
  4. Supervisory signal-initiating device - answers> An initiating device, such as a valve supervisory switch,that triggers a supervisory signal.
  5. Testing - answers> A procedure used to determine the status of a system as intended by conducting periodic physical checks on water based fire protection systems such as waterflow tests, fire pump tests, alarm tests, and trip tests of dry pipe, deluge, or preaction valves. These tests follow up on the original acceptance test at intervals specified in the appropriate chapter of NFPA #25, 2002 edition.
  6. Upright Sprinkler - answers> A sprinkler designed to be installed in such a way that the water spray is directed upwards against the deflector.
  7. Water Spray Fixed System - answers> A special fixed pipe system connected to a reliable fire protection water supply and equipped with water spray nozzles for specific water discharge and distribution over the surface or area to be protected. The piping system is connected to the water supply through an automatically or manually actuated valve that initiates the flow of water. An automatic valve is actuated by operation of automatic detection or manual release equipment installed in the same areas as the water spray nozzles. (In special cases, the automatic detection system may also be located in another area.)
  8. PREACTION SPRINKLER SYSTEMS - answers> designed for situations where there is danger of serious water damage. Water damage is usually caused by damaged sprinklers or broken piping. Under normal conditions there is no water in the piping. The air in the piping may or may not be is under pressure. A preaction valve prevents the water from entering the system. The valve is automatically opened when a fire detection system discovers that there is a fire or smoke condition. The preaction valve is tripped by the fire detection system before any of the

sprinkler heads open. A supervisory device signals when the valve is opened. The preaction valve can also be operated manually.

  1. DELUGE SPRINKLER SYSTEMS - answers> equipped with open sprinkler heads designed to wet down an entire area involved in a fire. This system is needed when there is danger of a fire rapidly spreading throughout the building. The deluge system will slow down the spread of the fire. Deluge systems are suitable for hazardous occupancies. This includes buildings in which flammable liquids or other hazardous materials are handled or stored.
  2. The sprinkler heads in the deluge system are open at all times. Under normal conditions there is no water in the piping. The air in the piping is not under pressure. A closed control valve prevents water from flowing into the system. A fire detection device automatically opens the control valve when a fire is identified. A supervisory device signals when the valve is opened. When the valve is opened water flows into the system. The water is then discharged out all of the sprinkler heads. The water control valve may also be opened manually.
  3. NON-AUTOMATIC DRY SPRINKLER SYSTEMS - answers> ll pipes are normally dry. Water is supplied when needed by pumping water into the system through the Fire Department connection. Some of these systems are supplied by manual operation of a water control valve and may be equipped with sprinklers with or without fusible links.
  4. There are several non-automatic systems: 1) Perforated pipe systems - a single line of piping drilled at intervals for water discharge. These systems are usually found in basements or other areas difficult to reach in fire fighting operations. 2) Open fixed spray nozzles for transformer vaults or other hazardous areas; 3) exterior exposure sprinklers (or window sprinklers) use open sprinkler heads to form an external water curtain on the walls of a building, and 4) Foam supply systems are used for the protection of special hazardous occupancies.
  5. Curb Valves - answers> Gate valves of the non-indicating type are provided in water distribution systems. Gate valves allow the sprinkler system to be shut off for repairs or maintenance. Such valves are normally a non-rising stem type. They are operated using a special key wrench. A valve box is located over the valve to keep dirt from the valve. The valve box also provides a convenient access point for the valve wrench to the valve nut. A complete record should be made for each valve in the system. This record should include the exact location, the date it was installed, the make, the direction of opening, number of turns to open, and any maintenance that was performed.
  6. The control valve for the building may also be on the outside wall or attached to an upright post, known as a post indicator valve (PIV). The building or section of the building controlled by the valve is usually marked on the post. The position of this valve (open or closed) is shown through a telltale opening in the post. On some posts, a padlock must first be opened to release the operating wrench or wheel handle.
  1. Pressure Maintenance Pumps (Jockey Pumps) - answers> Pressure maintenance pumps,
  2. Some times referred to as jockey, or makeup pumps, are often found on sprinkler systems. These pumps are designed to automatically operate when there is a slight drop in pressure due to the leakage in the system or a pressure surge. The jockey pump restores the pressure in the fire protection system to the desired level. When the drop of pressure in the system greater than the capacity of the jockey pump the fire pump is activated.
  3. Booster pumps/special service pumps - answers> Booster pumps are sometimes used in sprinkler systems. They small pumps with limited power are usually located in the basement or taking suction from gravity tanks. The booster pump is used when the water pressure available at the highest sprinkler head does not quite meet the needs of the sprinkler system. This small pump increases the water pressure in the sprinkler system until it reaches acceptable levels. The booster pump should not be confused with the fire pump or the jockey pump.
  4. Sprinkler system piping - answers> Branch lines are directly connected to sprinkler heads.
  5. Cross mains or loop mains are directly connected to branch lines. Feed mains are directly connected to cross mains or loop mains. Risers are able to supply feed mains or cross mains directly.
  6. rti - answers> response time index
  7. full flow test - answers> performed every 5 years:
  8. open main valve to let debris escape, then close
  9. system air a nd water pressrue recorded.
  10. relieve pressure by opening inspector test valve (use stopwatch)
  11. at dry pipe valve note aire pressure which valve trips an note time
  12. at inspectors test note time that water flows steadily.
  13. test terminated when clean water flows (shit valve)
  14. compare to past tests
  15. fire hydrant - answers> A valve connection on a water supply system having one or more outlets and that is used to supply hose and fire department pumps with water.
  16. Control valve - answers> A valve controlling flow to water base fire protection system. Control valve do not include hose valves
  1. Fire pump locations - answers> the fire pump should be located in a place that is noncombustible or fire resistant. has to be heated to a minimum of 40 degrees Fahrenheit.
  2. Gravity tanks should be how high above the highest sprinkler head? - answers> 25 feet.
  3. What are the three methods to heating a gravity tank - answers> Hot water circulation
  4. Steam is discharged directly into the tank
  5. steam coils are placed inside the tanks
  6. Heat from the sun is used
  7. Automatic fill pumps supply the water to most gravity tanks. The pumps fill the tank at a rate of __ gpm - answers> 65
  8. Centrifugal pump can pump at a rate of - answers> 25 to 5000 gallons per minute
  9. what is a fire hydrant? - answers> A valve connection on a water supply system having one or more outlets and that is used to supply hose and fire department connections with water.
  10. What is the purpose of gate valves? - answers> A valve controlling flow to water based fire protection systems. Is used to isolate,shut off, and open sprinkler systems.