S-12 S-13 Standpipe and Sprinkler Practice Questions With Correct Verified Answers
Typology: Exams
1 / 9
This page cannot be seen from the preview
Don't miss anything!
After the fire department appears on the scene, what should the fire brigade do? - โ โ Report to the Fire Command Station
In a fully sprinklered Class E building, how large can an area be before a fire wall is required to compartment the area? - โ โ Unlimited. (The sprinkler system should suppress the fire, which allows unlimited areas. This is true only in Class E buildings.
If you're looking at a stairway door and see a number on the door, which of the following is true? - โ โ You're on the stair side of a door
What kind of fire extinguisher is NOT allowed in kitchens? - โ โ H2O. Water would spread the fire
Upon activation, where should the fire brigade report? - โ โ To the stairway of the floor below the fire floor
Which of the following is NOT true about the Building Evacuation Supervisor? - โ โ Is required to have a Certificate of Fitness
How many sprinkler heads must be available, and where must they be stored? - โ โ Six Spares, stored at the main shutoff valve.
Where is the fire alarm single NOT required to sound? - โ โ Building Manger's Office
Which is NOT a required feature of a Class E fire alarm system? - โ โ Sprinkler System
When are locks allowed on elevator door? - โ โ When locks can be operated by city-wide standard elevator key. (1620 and 2642)
A Class E building has five tenants on each floor. Four have 7,500 sq. ft. each, the other has 22,500 sq. ft. How many fire wardens are required on the floor? - โ โ One for each 7,500 foot occupancies, and three for the 22,500 foot area.
In an actual emergency, how would you evacuate a handicapped person? - โ โ Take him to a designated stairway.
Which of the following keys should operate the smoke purge switch? - โ โ 1620- under the direction of the Fire Department Incident Commander
Which of the following is NOT true about the fire brigade? - โ โ They use fire hoses to fight fires.
Local Law 5 is the NYC law that - โ โ regulated office buildings.
Which of the following should function during phase 1? - โ โ Safety Edge
Which of the following is NOT true about cap colors of siamese connections? - โ โ Yellow means that there are both standpipes and non-automatic sprinklers.
Which of the following is true about the main shut off valve of an automatic sprinkler system? - โ โ Must be visually inspected weekly unless equipped with a temper switch.
In case of fire, when directed by the Fire Safety Director what should the alarm box runner do? - โ โ Go to the nearest FDNY alarm box, activate the alarm, respond verbally if necessary, and wait for fire engines to arrive.
A contractor tells you that he has to turn off the sprinkler system in order to replace some sprinkler heads. Which of the following are you NOT required to notify? - โ โ FDNY High Rise Unit
All are true about smoke detectors EXCEPT - โ โ visually inspected monthly.
All of the following must be done EXCEPT - โ โ Operational test of portable fire extinguishers
How often must activation of each manual sending station and verification of alarm receipt at the fire command station be done? - โ โ Semi-Annually (6 months)
Instructions for range hoods should be kept - โ โ in the kitchen at the entrance under glass
Which is true about the portable fire extinguishers? - โ โ Inspected monthly, maintenance performed annually, hydrostatically tested every five or 12 years, depending on the type.
All of the following must be checked monthly EXCEPT - โ โ Inspection/Cleaning of Range Hoods and Filters in Kitchens.
"Fail-safe" stairway door locks in a Class E building must unlock - โ โ every 4th floor
During an inspection of the sprinkler system, you notice that the sprinkler heads in one of the tenant's areas have all been painted the same color as the ceiling. What should you do? - โ โ Have the sprinkler heads replaced.
At what temperature range will a sprinkler head rated "ordinary" operate? - โ โ 135-165ยฐ F
Which statement is true? - โ โ A scissors stairs has a standpipe at every other floor.
At every elevator landing there must be a sign reading: - โ โ "In case of fire use stairs unless otherwise instructed"
While conducting a test of smoke detectors on the 26th floor, you receive alarms from smoke detectors on the 1st and 2nd floors. What would be you best course of actions? - โ โ Acknowledge the first and second floor alarms and call in an alarm to the Fire Department.
How often must fire drills be conducted in a new Class E building? - โ โ Every three months, for the first two years of occupancy. Every six months thereafter.
The emergency generator must have enough fuel to supply the total emergency power load for at least - โ โ 6 hours
Where must the lobby elevator ket switch be located? - โ โ No more than 4 feet from call button
"Fail Safe" when referred to in locks, means - โ โ that the door can be opened if the power fails
One morning you are notified the roof gravity tank heater has burned out. Which of the following are you required to notify? - โ โ Building Owner
The function of the upper check valve is to prevent - โ โ Back flow into the gravity tank
The primary duty of a fire brigade is to - โ โ evacuate occupants of building
How often must communication to Central Station from the FSC be checked? - โ โ Monthly
If the stem extends from an OS&Y valve, it is an indication that the valve is - โ โ open
What is a "blind" shaft way? - โ โ A floor where elevator cannot stop because there are no hoist way doors.
Which of the following is NOT true about stairway pressurization? - โ โ Required in addition to sprinklers.
How often must sprinkler heads be changed? - โ โ Only after activation
Elevators will be recalled by any of the following except - โ โ Manual pull station. Another vandalism-type prevention.
Which is true about plenums and raceways? - โ โ Plenums are in ceiling and Raceways are in floors
Which of the following is NOT required duty of Deputy Fire Safety Directors? - โ โ Maintain records as required by law
Which of the following would be considered inflammable? - โ โ Puddle of gasoline
What is a roof manifold used for? - โ โ Fight roof fires, Testing water flow
Which of the following is NOT required of floor wardens? - โ โ Certificate of Fitness
The 17th floor of a fully sprinklered J1 building has an area of 17,500 sq. ft. How many 2 1/2 gallons water extinguishers are required? - โ โ 3
Which of the following is NOT the duty of the Fire Safety Director? - โ โ Provide the Fire Safety Plan
Which of the following should NOT operate in a normal manner during phase 2? - โ โ Door Open Button
A hotel is 60 ft tall and 40 sleeping rooms of which 10 are occupied. How many fire safety directors are required? - โ โ 1
When torch operations are done, the fire watcher must check for fire - โ โ during the operations, when the operations are complete, a half hour later and a half hour after that
Diagrams require to be mounted in the hallways which show elevators, fire exits, etc. are called - โ โ floor diagrams
When a sprinkler head is said to "have fused" it means that it - โ โ was exposed to the temperature at which it was designed to activate.